The hazards of over-voltage are well known and these voltage fluctuations constitute a serious problem for users of most of the electrical equipments. Servo controlled AVR's are designed and manufactured by us for the healthy operation of sophisticated equipments. Our Electro Servo Motor Controlled AVAR’s are high speed electromechanical regulators, manufactured from the highest quality raw materials available. Superior transformer design and top quality raw material used in our Servo’s makes them highly efficient in handling any voltage fluctuations in the main supply
Single Phase | Three Phase | |
---|---|---|
Input Volts* | 100-260V | 200-440 |
Output Volts* | 230 +/- 1% | 380/400/415 +/-1% |
Efficiency | >95% | >98.5% |
Frequency | 48-52 Hz | 48-52 Hz |
Wave Form Distortion | Nil | Nil |
Temperature | Depends on type of cooling and IS Specifications | |
Environment | Designed for indoor tropical use |
How to choose a Servo Stabilizer
The neutral needs to be solidly grounded for proper functioning of the electrical system.
Banks and offices | |
---|---|
CNC Machines | Air Conditioning Plants |
Telecommunication Networks | Motor Loads |
Data Processing Equipment | Bio Medical Equipment |
Drives, PLC's | Induction Heating |
Hotels | Defense Application |
Industrial Units | Lighting Loads |
Residential | Farm Houses |
R & D Institutions | Sophisticated Laboratories |
Fault | Remedies | |
---|---|---|
1) | Output voltage Unbalanced |
1. Check input supply weather all 3 phases are present. If so ; 2. Carbon brush may have worn out broken. 3.Snapped or loose; connection on input/output. Correct the same. |
2) | Output voltage Fluctuating Continuously |
i) Adjust P3 plot clockwise on the servo control card till fluctuation stop. This can be done only on auto mode. ii)The carbon may be worn out and is causing sparkling on the track. Change the carbon. iii)Check for any loose connection on the input or the output side. |
3) | Continuous Rattling/hunting Sound |
i) Adjust P3 plot clockwise on the servo controlled card. Keep switching in ‘auto’ mode. ii) The gear on the motor and the main gear mismatching. Adjust the motor by loosening it four holding screws and moving the motor to match the two gears. Tighten the motor in the correct position. |
4) | Output voltage not Regulating |
i) Put the switch in manual mode and try to raise or lower the output voltage. ii) Check if the motor is running. Incase no change in voltage occurs; the gear on the motor shaft is definitely not matching with the main gear. Please do the needful as explained above. iii) Put the switch in auto mode after correction. If still not regulating to the correct value the control card may be defective. Before removing the control card short terminal No. 5 & 6 and then check. If still no function in output voltage occurs , change the card. iv) The voltage adjust pot provided on the front panel may be open, change the pot. |
5) | Tank over – heating Beyond limits |
i) Check for overloading on all three phases. The normal temperature of the oil should not be more than 45 degrees centigrade above the ambient. If the temperature is more there may be some short in the winding. Thus, requiring a major repair. ii) The oil might have fallen due to some leakage and this can also result in overheating. |